Appendix C: System Initial Startup

Appendix C: System Initial Startup

WARNING: Before starting up the system, ensure that all isolation valves are fully open and all vessel drains are fully closed. Failure to do so may result in improper system operation.

1.    SYSTEM STARTUP

FIRST WAVE SPROUT/10/40/85:              V/P/G/SP-XXX-1

FIRST WAVE 185:                                      V/P/G/SP-XXX-1/2

Follow the steps below to start up the system:

  1. Ensure that all drains and sample valves are closed.
  2. Verify that the Emergency Shutdown (ESD) button is pulled out.
  3. Clear any alarms from the system.
  4. Set the chemical feed pumps (P-150B-1/2) to AUTO mode.
  5. Set the Microscreen(s) (G-170-1/2, P-170-1/2) to AUTO mode.
  6. Set the screw press(es) (SP-130-1/2) to Auto mode.
  7. Ensure that the polymer tanks have freshly made polymer in them and are full.
    Refer to the "Chemical Make Down" section for instructions.
  8. Fill all the tanks (V-170-1/2, V-130B) halfway.
  9. Set the inlet feed pump (P-120) to AUTO mode and adjust the desired flow rate according to the table below. The pump should start and begin feeding water into the system.

TECHNOLOGY PLATFORM

INLET PUMP INITIAL FLOW RATE GUIDE (GPM)

FIRST WAVE Sprout

4

FIRST WAVE 10

30

FIRST WAVE 40

65

FIRST WAVE 40 HIGH FLOW

150

FIRST WAVE 85

90

FIRST WAVE 85 HIGH FLOW

250

FIRST WAVE 185

175

FIRST WAVE 185 HIGH FLOW

500

 

Note:
If the system is a 2-screen system (ie: First Wave 185 or First Wave 185 High Flow), it is important to ensure that the motorized valves on the inlet piping are set to distribute 50% of the flow to each screen. This ensures balanced operation and proper utilization of both screens.

Please verify and adjust the motorized valves on the inlet piping to achieve an equal distribution of flow between the two screens. This can be done by adjusting the valve positions accordingly. By setting the valves to send 50% of the flow to each screen, you can optimize the performance of the system and ensure effective solids removal.

2.    ADJUSTING THE INLET FEED PUMP FLOW RATE

To adjust the flow rate of the inlet feed pump, follow these steps:

  • Access the touchscreen interface.
  • Locate the flow rate adjustment control for the inlet feed pump.
  • Input the desired flow rate using the touchscreen or numeric input.
  • Verify the new flow rate using the flow meter mounted on the pump discharge or check the flow rate displayed on the HMI.
  • After adjusting the flow rate, the inlet pump and chemical feed pumps will automatically adjust their flow rates based on the new setting.

3.    ADJUST THE TRANSFER PUMPS

To adjust the transfer pumps, which include the screw press liquids (P-130B) and the filtrate (P-170B) pumps, follow these steps:

  • Ensure that the pumps are in AUTO mode on the HMI.
  • Access the VFD controls on the HMI to adjust the motor speed of the transfer pumps.
  • Ensure the PID controls are set to AUTO on the HMI.
  • Adjust the desired level setpoint in the corresponding feed tanks to regulate the transfer pump operation.
  • Monitor the transfer pumps to ensure they are running steadily and not cycling on and off.

4.    INITIAL OPERATING INSTRUCTIONS

Follow these instructions for the initial operation of the system:

  • The system should automatically control all the flows based on the inlet flow rate.
  • The polymer dosing pumps (P-150B-1/2) should be in AUTO mode on the HOA screen.
  • The PID loop should be set to AUTO mode for automatic control of the pumps.
  • If the system is equipped with grōCONTROL, it should be initially set to MANUAL mode on start-up. After running for 30 minutes and confirming TSS measurements on both the inlet and filtrate liquids, grōCONTROL can be switched to AUTO mode for automated dosing control.
  • Ensure that the flow is evenly distributed across the floc tank spillway and the Microscreen screen.
  • Check the spray bar to ensure it is spraying evenly across the microscreens and moving up and down. Adjust the P-170-1/2 NORMAL speed to maintain a spray that is sufficient to keep solids sliding down the screen without excessive accumulation. Adjust the P-170-1/2 CLEAN speed to ensure it fully clears off all solids from the microscreen during the predetermined clean mode intervals.
  • Monitor the transfer pumps (P-170B, P-130B) to ensure they maintain the operator-set level, run steadily, and do not cycle on and off.


    • Related Articles

    • 2. System Startup and Shutdown

      SYSTEM STARTUP AND SHUTDOWN WARNING: Before starting up the system, ensure that all isolation valves are fully open, and all vessel drains are fully closed. Refer to Appendix C for initial startup procedures. STARTUP Before initiating the system ...
    • SW APPENDIX A: INITIAL SYSTEM STARTUP

      WARNING: Ensure all isolation valves are fully open and that all vessel drains are fully closed prior to the startup of the system. Ensure that all the RO Clean in Place (CIP) Valves are fully closed. STARTUP SECOND WAVE STARTUP – CLARIFIER AND ...
    • 2. SYSTEM STARTUP AND SHUTDOWN

      WARNING: Ensure all isolation valves are fully open and that all vessel drains are fully closed prior to the startup of the system. Ensure that all the RO Clean in Place (CIP) Valves are fully closed. For Initial Startup of the Second Wave, Refer to ...
    • Appendix B: groControl System

      The grōCONTROL system is designed to enhance the operation of the First Wave system by automating the TSS (Total Suspended Solids) and pH readings of the process liquids at specified time intervals. When grōCONTROL is activated, it will automatically ...
    • APENDIX A: THE POLYFAST SYSTEM

      LWR’s PolyFAST unit is specifically designed to automatically prepare a 0.5% concentration of grō17 polymer, ensuring smooth system operation with minimal supervision or operator intervention. It is essential to calibrate the unit during the initial ...