2. System Startup and Shutdown
SYSTEM STARTUP AND SHUTDOWN
WARNING: Before
starting up the system, ensure that all isolation valves are fully open, and
all vessel drains are fully closed. Refer to Appendix C for initial startup
procedures.
STARTUP
Before initiating the system startup, follow these steps:
- Check that all drains and sample valves are
closed.
- Ensure the Emergency Shutdown (ESD) button is
pulled out.
- Clear any alarms from the system.
- Place the chemical feed pump (P-150B-1) in the "AUTO" mode.
- Place the Microscreen (G-170-1, P-170-1) in the
" AUTO " mode.
- Place the screw press (SP-130-1) in the " AUTO " mode.
- Repeat the above steps for any P/G/SP-XXX-2 if operating a FW-185 system
- Place the inlet feed pump (P-120) in the
" AUTO " mode. The pump should start and begin feeding water
into the system.
1. ADJUSTING
THE INLET FEED PUMP FLOW RATE
- The inlet feed pump is equipped with a Variable Frequency Drive (VFD) to
adjust the flow rate.
- Adjust the pump speed
through the touchscreen interface.
- Verify the new flow rate
using the flow meter mounted on the pump discharge.
After adjusting the flow rate, the chemical
feed pumps will automatically adjust their flow rates accordingly.
2. ADJUSTING
THE TRANSFER PUMPS
To adjust the other pumps in the system, you can use either of the
following methods:
Move the throttling or bypass valves located
in their discharge lines.
Adjust the speed of the motor using the VFD
Controls.
SYSTEM SHUTDOWN
To properly shut down the system, follow these steps:
Place the inlet feed pump (P-120) in the
"OFF" position.
After shutting down the inlet feed pump, allow
the system to pump down the water in the filtrate tank. Once the tank has
been pumped down to its setpoint, you can proceed to the next
step.
Press the Emergency Shutdown (ESD) button
located on the front of the main control panel. This button is used to
initiate an immediate shutdown of all pumps in the system.
EMERGENCY SHUTDOWN
In the event of a system upset or emergency, you can perform an
immediate shutdown by following these steps:
Locate the Emergency Shutdown Button (ESD) on
the front of the main control panel.
Press the ESD button. This action will
immediately stop all pumps in the system.
Related Articles
2. SYSTEM STARTUP AND SHUTDOWN
WARNING: Ensure all isolation valves are fully open and that all vessel drains are fully closed prior to the startup of the system. Ensure that all the RO Clean in Place (CIP) Valves are fully closed. For Initial Startup of the Second Wave, Refer to ...
Appendix C: System Initial Startup
WARNING: Before starting up the system, ensure that all isolation valves are fully open and all vessel drains are fully closed. Failure to do so may result in improper system operation. 1. SYSTEM STARTUP FIRST WAVE SPROUT/10/40/85: V/P/G/SP-XXX-1 ...
SW APPENDIX A: INITIAL SYSTEM STARTUP
WARNING: Ensure all isolation valves are fully open and that all vessel drains are fully closed prior to the startup of the system. Ensure that all the RO Clean in Place (CIP) Valves are fully closed. STARTUP SECOND WAVE STARTUP – CLARIFIER AND ...
Appendix B: groControl System
The grōCONTROL system is designed to enhance the operation of the First Wave system by automating the TSS (Total Suspended Solids) and pH readings of the process liquids at specified time intervals. When grōCONTROL is activated, it will automatically ...
APENDIX A: THE POLYFAST SYSTEM
LWR’s PolyFAST unit is specifically designed to automatically prepare a 0.5% concentration of grō17 polymer, ensuring smooth system operation with minimal supervision or operator intervention. It is essential to calibrate the unit during the initial ...