13. GENERAL TROUBLESHOOTING

13. GENERAL TROUBLESHOOTING

SYMPTOM

CAUSE

ACTION

System won't start

ESD Button Pushed

Check that all ESD buttons are in their "OUT" position.  Press 'RESET' Button

Main Feeder Protection Tripped

Check feeder protection for blown fuse or tripped circuit breaker.  Check wiring for faults.

Motor Overload Tripped

Check overload relays for flag indication.  Press overload 'RESET' Button.  Check overload setting and match to motor FLA, if set above motor FLA.  Check pump for maintenance.

PLC in 'Stop' mode 

Check the position of the Run/Stop switch on PLC and toggle from RUN to STOP and back to RUN

If problem persists, contact LWR.

Motor won't run in HAND or AUTO

ESD Button Pushed

Check that all ESD buttons are in their "OUT" position.  Press 'RESET' Button

Main Feeder Protection Tripped

Check feeder protection for blown fuse or tripped circuit breaker.  Check wiring for faults.

Motor Overload Tripped

Check overload relay for flag indication.  Press overload 'RESET' Button.  Check overload setting and match to motor FLA, if set above motor FLA.  Check pump for maintenance

Motor Thermistor Opened

Allow motor to cool and try again.  If thermistors open, check system voltage, and motor current.  If ok, check pump for maintenance.

PLC in 'Stop' mode 

Check the position of the Run/Stop switch on PLC and toggle from RUN to STOP and back to RUN

If problem persists, contact LWR

Motor won't run in AUTO

ESD Button Pushed

Check that all ESD buttons are in their "OUT" position.  Press 'RESET' button.

Main Feeder Protection Tripped

Check feeder protection for blown fuse or tripped circuit breaker.  Check wiring for faults.

Motor Overload Tripped

Check overload relay for flag indication.  Press overload 'RESET' button.  Check overload setting and match to motor FLA, if set above motor FLA.  Check Pump for maintenance.

Motor Thermistor Opened

Allow motor to cool and try again.  If thermistors open, check system voltage, and motor current.  If ok, check pump for maintenance.

PLC in STOP mode

Check the position of the RUN/STOP switch on PLC and toggle from RUN to STOP and back to RUN.

Alarm Condition Exists

Clear alarm condition, restart unit.  If alarm occurs again, check system adjustment.

If problem persists, contact LWR.

Motor cycles on and off

Motor Overload Tripped

Check overload relay for flag indication.  Press overload 'RESET' Button. Check to see if relay set to automatically reset.  Check overload setting and match to motor FLA, if set above motor FLA.  Check pump for maintenance.

Motor Thermistor Opened

Allow motor to cool and try again.  If thermistors open, check system voltage, and motor current.  If ok, check pump for maintenance.

If problem persists contact LWR

Water/Chemical on Floor

Piping leak

Find leak and repair.

Vessel leak 

Find leak and repair.

Pump leak

Diagnose point of failure (seal, bearing) and repair as per OEM manual.

If problem persists, contact LWR.

System Performance Reduced

System out of adjustment

Adjust valving to balance flow through the system.

Adjust chemical dosing.

Perform jar test to identify ideal chemistry. If more than 5% above or below anticipated dose, ensure proper polymer make down.

If problem persists contact LWR

Pump flow is reduced or zero when pump is running

Restriction in line

Ensure all valves on process piping are open.

Check for pressure building in discharge line. If pressure is increasing, disassemble discharge piping after pressure gauge to identify blockage. If no pressure, disassemble suction piping and discharge piping before pressure gauge to identify blockage.

Incorrect VFD parameters

Use VFD OEM manual to identify motor nameplate parameter settings and verify they match the motor nameplate.

Improper motor functioning

Check motor rotation.  If motor is running backwards reverse any two motor leads to change direction.

If problem persists, disassemble pump to determine failure.

If problem persisits, contact LWR

Pump is flowing but no flow is registered on HMMI

Analog error

See analog error troubleshooting.

Flow meter error displayed

Check code in OEM manual.

If problem persists contact LWR

Analog Device Error

Device has no power

Consult single line diagram and ensure main power fuse for device is closed and intact.

Analog input card has no power

Consult single line diagram and ensure analog input card fuse is closed and intact.

Analog input channel has no power

Consult single line diagram and ensure the analog input channel for the associated device is closed and intact.

Corrosion on wire terminals.

Disconnect device from power at the control panel. Starting from the device end, disconnect ±24V wires and clean terminals with a stiff wire brush. Cut and strip back wires and replace.

If problem persists, contact LWR

Cartridge filters require changing more frequent than once every 24hrs

Solids content too high

Adjust First Wave operation to get down to 98.5% removal of inlet solids, achieving a TSS below 1000ppm

Check clarifier sludge level. Increase sludge pump speed if sludge levels at the 2nd and 3rd sample valve are within 200ppm.

Excess polymer blinding filter pores

Observe microscreen solids and check for excessive foaming in vessels. Reduce polymer dose accordingly.

If problem persists, contact LWR

High RO Permeate TDS from one or more vessels.

Damage to RO membrane

 Inspect all membranes, adaptors, and O-rings for visible damage in each identified vessel.

Membrane installed incorrectly

Remove all membranes from problematic vessel and reinstall in the correct orientation.

If problem persists, contact LWR

RO requires cleaning more than once every 24hrs

RO recovery too high

Open concentrate globe valve slowly to reduce recovery rate to 65-70% of RO feed volume.

Memebranes fouled

Perform manual cleaning procedure to remove fouling.

Solids content too high

Adjust First Wave operation to get down to 98.5% removal of inlet solids, achieving a TSS below 1000ppm.

Check clarifier sludge level. Increase sludge pump speed if sludge levels at the 2nd and 3rd sample valve are within 200ppm.

Excess polymer blinding membrane pores

Observe microscreen solids and check for excessive foaming in vessels. Reduce polymer dose accordingly.

If problem persists, contact LWR


    • Related Articles

    • 12. General Troubleshooting

      SYMPTOM CAUSE ACTION System won't start ESD Button Pushed Check that all ESD buttons are in their "OUT" position. Press 'RESET' Button Main Feeder Protection Tripped Check feeder protection for blown fuse or tripped circuit breaker. Check wiring for ...
    • APENDIX A: THE POLYFAST SYSTEM

      LWR’s PolyFAST unit is specifically designed to automatically prepare a 0.5% concentration of grō17 polymer, ensuring smooth system operation with minimal supervision or operator intervention. It is essential to calibrate the unit during the initial ...
    • 4. Microscreen Setup and Operation

      MICROSCREEN Microscreen Setup Proper setup of the Microscreen involves adjusting two devices to ensure effective draining of solids through the screen surface. These devices are the floc tank adjustment and the screen angle adjustment. FLOC TANK ...
    • 3. Chemistry Setting Adjustment

      CHEMISTRY SETTING AND ADJUSTMENT Goals of Chemical Treatment System Type Microscreen filtrate TSS Size of flocs on microscreen Strength of flocs on microscreen Goals First Wave System <15% of Inlet Manure TSS Large Strong Goals Plant System (Second ...
    • 6. Floc Tank Setup, Optimization and Operation

      FLOCCULATION TANK The flocculation tank plays a crucial role in the treatment process by mixing the injected polymer with the manure before it flows over the Microscreen unit. To ensure effective floc formation while minimizing the use of chemicals, ...